Page 1 - Cascade systems Quinta Pro

Great BritainENCascade systems Quinta ProInstallation andService Manual124823-01

Page 2 - Contents

4 Cascade system components4.1 GeneralThe cascade systems consist of the following components:4 Main pipes.4 Low loss header.4 Boiler pump.4 Boiler co

Page 3

4.3 Low loss headerThe low loss headers have the following connecting flanges:4 Low loss header for main pipes with diameter = 65 mm up to aheat outpu

Page 4

4.5.1. Connection kit with pumpÙFlow connection:(1¼" female thread to boiler and 35 x 1,5 mm to mainpipe):ÚReturn connection:(1¼" female th

Page 5 - 1 Introduction

4 Gas filter extension piece (for fitting gas filter next to low lossheader) DN 50 and DN 65 (To be used when gas filter is fitted onthe same side as

Page 6

5 Installation drawings for cascadesystems5.1 GeneralThe cascade systems can be divided into 3 main groups:4 2 to 6 boilers in a linear configuration,

Page 7 - 2.5 Output control

5.2 Wall-mounted linear configuration - LW5.2.1. Installation drawing with 2 boilers - LWASystem flow; connection DN 100 / DIN 2631 (8 holes)BSystem r

Page 8 - 3 Remeha cascade systems

5.2.2. Installation drawing with 3 boilers - LWASystem flow; connection DN 100 / DIN 2631 (8 holes)BSystem return; connection DN 100 / DIN 2631 (8 hol

Page 9

5.2.3. Installation drawing with 4 boilers - LWASystem flow; connection DN 100 / DIN 2631 (8 holes)BSystem return; connection DN 100 / DIN 2631 (8 hol

Page 10 - 4 Cascade system components

5.2.4. Installation drawing with 5 boilers - LWASystem flow; connection DN 100 or 125 / DIN 2631 (8holes)BSystem return; connection DN 100 or 125 / DI

Page 11 - 4.5 Boiler connection kits

5.2.5. Installation drawing with 6 boilers - LWASystem flow; connection DN 100 or 125 / DIN 2631 (8holes)BSystem return; connection DN 100 or 125 / DI

Page 12 - 4.7 Accessories

Contents1 Introduction ...41.1 General ...

Page 13 - 230413 - 124823-01

5.3 Free-standing linear configuration - LV5.3.1. Installation drawing with 2 boilers - LVASystem flow; connection DN 100 / DIN 2631 (8 holes)BSystem

Page 14 - 5.1 General

5.3.2. Installation drawing with 3 boilers - LVASystem flow; connection DN 100 / DIN 2631 (8 holes)BSystem return; connection DN 100 / DIN 2631 (8 hol

Page 15

5.3.3. Installation drawing with 4 boilers - LVASystem flow; connection DN 100 / DIN 2631 (8 holes)BSystem return; connection DN 100 / DIN 2631 (8 hol

Page 16

5.3.4. Installation drawing with 5 boilers - LVASystem flow; connection DN 100 or 125 / DIN 2631 (8holes)BSystem return; connection DN 100 or 125 / DI

Page 17

5.3.5. Installation drawing with 6 boilers - LVASystem flow; connection DN 100 or 125 / DIN 2631 (8holes)BSystem return; connection DN 100 or 125 / DI

Page 18

5.4 Back-to-back configuration - RG5.4.1. Installation drawing with 3 boilers - RGASystem flow; connection DN 100 / DIN 2631 (8 holes)BSystem return;

Page 19

5.4.2. Installation drawing with 4 boilers - RGASystem flow; connection DN 100 / DIN 2631 (8 holes)BSystem return; connection DN 100 / DIN 2631 (8 hol

Page 20

5.4.3. Installation drawing with 5 boilers - RGASystem flow; connection DN 100 or 125 / DIN 2631 (8holes)BSystem return; connection DN 100 or 125 / DI

Page 21

5.4.4. Installation drawing with 6 boilers - RGASystem flow; connection DN 100 or 125 / DIN 2631 (8holes)BSystem return; connection DN 100 or 125 / DI

Page 22

6 Independently installed cascade systems6.1 GeneralIt is also possible to have an independently installed cascade systemconsisting of several units.

Page 23

5.2.5 Installation drawing with 6 boilers - LW ...185.3 Free-standing linear configuration - LV ...195.3.1 Installation drawing

Page 24

6.2 Standard cascade system1Cascade controller 2Boiler pump3Safety valve4Non-return valve5Manual seal6Air vent7Low loss header8Drain cock9Flow sensor

Page 25

6.3 Dimensioning a standard low loss headerXBoiler-side connectionYSystem-side connectionThe low loss header serves to isolate the boiler circuit from

Page 26

For the installation of 2 or 3 Quinta Pro 30, Quinta Pro 45 and/orQuinta Pro 65 wall-hung boilers, our range of products includesspecial compact low l

Page 27

Quinta Pro 65ΔPBoiler resistanceM3/hFlow rateQuinta Pro 90ΔPBoiler resistanceM3/hFlow rateQuinta Pro 115ΔPBoiler resistanceM3/hFlow rate6.6 Non-return

Page 28

boiler(s) must have an additional expansion vessel. This also appliesif part of the system is isolated by means of a heat exchanger.6.9 Configuration

Page 29 - 6.1 General

7 Gas connection7.1 GeneralThe boilers are suitable for use with all types of natural gas andpropane category II2H3P. Connect the boilers to the gas m

Page 30 - 6.2 Standard cascade system

8 Connections for the air and exhaust pipes8.1 GeneralThe boilers can be used in room-ventilated or room-sealedoperation. The room-open version extrac

Page 31

8.4 Material requirementsWhen combining different metals, these must be galvanicallyisolated. Galvanic isolation (rubber inlay) is also required when

Page 32 - 6.5 Boiler and system pumps

9 Exploded view9.1 Exploded viewT003303-B 1021 1022 1019 1018 1005 1018 1019 1017 1010 1021 1022 1023 1024 1003 1021 1022 1021 1022 1023 1024 1018 100

Page 33 - T003292-A

T003424-A2008 2009 2018 2013 2019 2001 2020 2015 2023 2013 2014 2003 20202014 2017 2021 2010 2014 2015 2014 2005 2014 2016 2015 2011 2019 2019 2020 20

Page 34

3230413 - 124823-01

Page 35 - 7 Gas connection

Markers Description Part1001Set of main pipes 100-4 11001Set of main pipes 100-3 11001Set of main pipes 100-2 11001Set of main pipes 65-4 11001Set of

Page 36 - 8.3 Joint flue gas discharge

Markers Description Part2007Set of insulation parts RG 12008Insulation parts for low loss header 12009Insulation for elbow 12010Boiler connection kit/

Page 39

Broag Ltd.Remeha HouseMolly Millars LaneRG41 2QP WOKINGHAM,Berks.Tel: +44 118 9783434Fax: +44 118 9786977Internet: uk.remeha.comE-mail: boilers@broa

Page 40

1 Introduction1.1 GeneralThis technical information contains useful and important informationfor proper dimensioning of a cascade system with wall-mou

Page 41

2 General description of cascade systems2.1 The optimum number of boilers in a cascadeIn many situations it is advantageous to spread the total requir

Page 42

2.2 Compact cascade configurationsThe boilers Quinta Pro 30/45/65/90/115 are particularly suitable foruse in a cascade configuration. Their width of o

Page 43

3 Remeha cascade systems3.1 GeneralIn order to make it as simple as possible to create a cascadeconfiguration, our product range has included complete

Page 44 - © Copyright

Boiler type Useful output [kW]50/30 °C 80/60 °CQuinta Pro 30 31.4 29.3Quinta Pro 45 43.0 40.0Quinta Pro 65 65.0 61.0Quinta Pro 90 89.5 84.2Quinta Pro